Chapter 2 System Installation

1-73

1

2

Visual KV

Series

Number of connectable units

When the basic unit is a KV-10xx/16xx/24xx

Up to four input units and four output units (that is, up to 8 total expansion units)
can be connected to one basic unit.

When the basic unit is a KV-40xx

Up to three input units and four output units (that is, up to 7 total expansion units)
can be connected to one basic unit.

When KV-E4XT/KV-E4XR expansion I/O units are connected

One I/O unit is regarded as two units (that is, one input and one output unit). For
example, when only expansion I/O units are connected to one basic unit, up to
four expansion I/O units can be connected. Up to three expansion I/O units can
be connected to a KV-40 xx basic unit.

Note 1: There are no restrictions about the order of connected expansion units.

Note 2: When connecting expansion units to an AC power type basic unit, be sure
that the total current consumption of all connected units does not exceed the output
capacity of the Visual KV Series basic unit. Otherwise, consider to use a DC power
type basic unit in conbination with an external DC power supply having enough
capacity.

Expansion units

Basic unit

Input

Output

Input

Input

Output

Output

Output

Input

Up to 8 units

Expansion units

Basic unit

Output

Output

Input

Output

Input

Output

Input

Up to 7 units

1
0

1
1

1
1

0
1

0
1

1
0

= 4
= 4

When two expansion I/O units are connected

Expansion units

Basic unit

Input

I/O

I/O

Output

Output

Input

6 units

Input
Output

2.2 Connecting Visual KV Series Expansion Units

KVHKA Chap 02.p65

08.3.11, 11:11 AM

73