Kv -300 – KEYENCE Visual KV Series User Manual
Page 285

7.5 KV Mode Programming
KV-300 Series Only
KV
-300
KV-10/80
Chapter 7 KV-L2 Serial Interface Module
1-261
1
7
E2
Program
unregis-
tered
• "M1" was transmitted with no
program stored in the KV-300
CPU.
• Reading of timer/counter was
attempted.
• Register a program into the
KV-300 CPU.
• Check the program for the
timer/counter number being
used and specify it.
E3
CPU fault
• Hardware error was detected
in a KV-300 CPU.
• Turn the power to the KV-300
OFF and then ON again. If
the cause of the error is not
corrected, the CPU may be
faulty. Contact your nearest
KEYENCE office.
E4
Write-
protected
• Attempt was made to change
the preset value of a counter,
timer, or CTC in a write-
protected program.
• Write-enable the program,
and change the preset value.
E5
CPU error
• "M1" was transmitted before
an error message was
cleared from the KV-300.
• Clear the error message from
the KV-300 CPU, and remove
the cause of the error.
Error code list
Error codes included in responses to the KV-300 CPU error check command (?E)
as well as error descriptions, causes of error, and remedies are listed below.
Error
Code
Description Cause
Remedy
00
No error
—
—
10
CALL nest
error
• Subroutines are nested to four
levels or more.
• These errors may occur when
a program is executed. Check
the program while paying
particular attention to usage of
subroutines and the INT
instruction, and restore the
program accordingly.
11
FOR nest
erro
• FOR-NEXT instructions are
nested to eight levels or more.
12
INT nest
error
• Five levels or more of inter-
rupts occurred simultaneously.
13
MPS nest
error
• MPS/MPP instructions are
nested to eight levels or more.
20
Memory
erased
• Contents of RAM are erased.
All data in data memory and
current values of counters in
the KV-300 CPU are cleared.
• Check data in data memory
and current values of counters,
and re-enter correct data. The
KV-300 CPU returns to normal
operation after the error is
cleared.
30
Scan time
error
• Scan time exceeds 300 ms.
• Check the program again.
• Be sure that there is no
excessive repetition using the
FOR-NEXT loop.
• Be sure that an interrupt is not
executed at a higher rate.
40
NO PRO-
GRAM
• An attempt was made to
operate the KV-300 CPU with
no program stored.
• Write a program into the
KV-300 CPU.
50
SND/RTN
failure
• Hardware error was detected
in a KV-300 CPU.
• Turn the power to the KV-300
OFF and then ON again. If
the cause of the error is not
removed, the KV-300 CPU
may be faulty. Contact
nearest KEYENCE office.
51
Division by
zero
52
Address
error
53
Invalid
instruction
54
Watchdog
timer error
KVHKA Chap 07_5to10.p65
08.3.11, 11:18 AM
261