KEYENCE Visual KV Series User Manual
Page 418
Appendix B Specifications and Dimensions
KV-300 Series
Appendicies
Appendices
1-394
AC Power supply module/DC power distribution module
Note 1: Do not install both the KV-U4 and KV-U5 within one system.
Note 2: The KV-U5 power supply interface module distributes 24 VDC to the
modules in the system. It requires a 24 VDC output power supply of sufficient output
current capacity.
Note 3: Install the KV-300 CPU to the right of the KV-U4/U5.
For KV-10/80 users
System specifications
Item
Specifications
Model
KV-U4
KV-U5
Input supply voltage
100 to 240 VAC ±10% (50/60 Hz)
24 VDC ±10%
Output voltage
24 VDC ±10%
–
Maximum output
1.4 A (Total of power supplied to connected
3.5 A
current
modules and service power supply)
Model
KV-10R(W)/10T(2W) KV-16R(W)/16T(2W) KV-24R(W)/24T(2W) KV-40R(W)/40T(2W)
KV-80R(W)/80T(W)
Arithmetic and
Stored program
control system
Programming
Ladder diagram and extended ladder diagram
language
Number of
Basic: 16, application :34, arithmetic: 26, interrupt: 4 (8 programs)
instructions
Execution time
1.0 µs min., 1.92 µs average
1.4 µs min., 3.12 µs average
(basic I/O
instructions)
Avg. number of
500 steps/program
3000 steps/program
steps
Input
6 inputs (70 max.)
10 inputs (74 max.)
16 inputs (80 max.)
24 inputs (72 max.)
48 inputs (80 max.)
Output
4 outputs (68 max.)
6 outputs (70 max.)
8 outputs (72 max.)
16 outputs (64 max.) 32 outputs (80 max.)
Internal utility
160
800
relays (with
latching function)
Special utility
160
relays
Data memory
1000 words
2000 words
(16 bits)
Temporary memory
32 words
(16 bits)
Timer/counter
A total of 64 timers, up-counters,
A total of 120 timers, up-counters, and up-down counters are
and up-down counters are provided
provided as follows:
as follows:
0.1-s timer (0 to 6553.5 s)
0.1-s timer (0 to 6553.5 s)
0.01-s timer (0 to 655.35 s)
0.01-s timer (0 to 655.35 s)
1-ms timer (0 to 65.535 s)
1-ms timer (0 to 65.535 s)
1 analog timer
2 analog timer
(0 to 24.9 s, 0 to 2.49 s, or 0 to 0.249 s) (two of 0 to 24.9 s, 0 to 2.49 s, or 0 to 0.249 s)
High-speed counter
2 auto-reset up-counters (max. input response frequency: 10 kHz)
High-speed counter
4
comparator
Direct clock pulse
2 kHz max. (output from 0500), 1.5 kHz max. (output from 0501)
20 kHz max. (output
from 0500), 1.5 kHz
max. (output from
0501)
Memory switch
16
Memory backup
Program memory: EEPROM, programs retained for 10 years min., rewritable 50,000 times min.
Data memory: data retained for 2 months min. by capacitors (at 25°C (77°F))
Expansion unit
4 units (max.)
3 units (max.)
Self-diagnosis
CPU and RAM errors
Peripherals
Handheld programmer KV-P3E(01), memory cards M-2 & M-3, card driver Z-1
KVHKA Appendix.p65
08.3.11, 11:05 AM
394