8.4 Programming
KV-300 Series Only
KV
-300
KV-10/80
Chapter 8 KV-AN6 Analog I/O Module
1-322
8
8.4.3
Output Characteristics (D/A)
On the KV-AN6, the analog output function converts digital (binary) data to analog
external output signals. The digital data stored in data memory is converted to
analog data and sent to an output unit at every scan time.
The analog output signal can be set according to the input range as shown in the
following table.
The selection switches in the table are located on the right side of the KV-AN6.
➮ Refer to page 1-319.
Voltage output
Selection switch
Description
Range
Voltage output
-5 to +5 V
-10 to +10 V
Connected to terminal for current output
Current output
4 to 20 mA
(Analog output value)
Current output
Through the D/A converter, digital data stored in the assigned data memory ad-
dresses by channel (Refer to page 1-324) is output as analog signals. The effective
bits are the 12 bits starting from the most significant digit.
Note: A change in the value of the DM address from 7FFFH (32767) to 8000H
(32768) or vice versa means that the polarity is reversed when the voltage output is
selected, or that output drastically changes from the maximum value to the minimum
value or vice versa when the current output is selected. Use the program to maintain
output data within the specified range.
0
10
8
6
4
2
-32000(8300H)
-25600
-19200
-12800
-6400
6400
12800
19200
25600
(7D00H)32000
-2
-4
-6
-8
-10
(V)
2
6400
12800
19200
25600
32000
-32000
-25600
-19200
-12800
-6400
(mA)
6
8
10
12
14
16
18
20
0
4
(±10 V range)
(±5 V range)
(Digital data)
(Analog output value)
(4-to-20 mA range)
(Digital data)