KV-300 Series Only
KV
-300
KV-10/80
Chapter 8 KV-AN6 Analog I/O Module
1-331
1
8
8.5.3
Specifications
Environmental specifications
System specifications
Model
KV-AN6
Maximum current consumption
240 mA
Ambient temperature
0 to 50 °C (32 to 122°F), No freezing
Relative humidity
35 to 85%, No condensation
Noise immunity
1500 Vp-p min., pulse width: 1 µs and 50 ns
(Noise generated by noise simulator)
Vibration
10 to 55 Hz, double amplitude of 1.5 mm max., applied
in each of X, Y, and Z directions (2 hrs)
(1 G when attached to a DIN rail)
Insulation resistance
50 MΩ between power terminal and I/O terminal, and
external terminals and housing (measured with 500
VDC megohmmeter)
Environmental restrictions
No excessive dust or corrosive gas
Weight
Approx. 200 g
Note: The A/D and D/A converters can be used simultaneously.
A/D specifications
D/A specifications
Analog input
Voltage ±10 V
Analog output
Voltage: ± 10 V
(switch selectable)
±5 V
(voltage output: switch
± 5 V
Current: 0 to 20 mA
selectable; current output:
Current: 4 to 20 mA
use separated terminal)
Input impedance
Voltage: 1 MΩ
Output impedance
Voltage: 100 Ω
Current: 350 Ω
Max. load resistance
Current: 400 Ω
Analog input channels 4 channels
Analog output channels
2 channels
Resolution
±10 V 5 mV (1/4000)
Resolution
±10 V 5 mV (1/4000)
±5 V 2.5 mV (1/4000)
±5 V 2.5 mV (1/4000)
0 to 20 mA 5 mA (1/4000)
4 to 20 µA 4 µA (1/4000)
Digital data format
16-bit binary, 2’s complement
Effective bits are the 12 bits starting from the most significant bit.
Total accuracy
±1% of full scale
Conversion rate
720 µs/4 ch
Conversion rate
360 µs/2 ch
Isolation method
Photocoupler: Not isolated between channels or between A/D and D/A converters
Absolute input
Voltage: ±12 V max.
Current: 30 mA max.
KVHKA Chap 08.p65
08.3.11, 11:19 AM
331