Separate-amplifier Proximity Sensor

ES-M1(P)/M2(P)

Instruction Manual

• The ES-M1/M2 are intended for target detection. Do not use

these products in a safety circuit for protecting the human
body.

• The ES-M1/M2 are not explosion-proof. Do not use these

products in an environment where inflammable gas, liquid or
powder is present.

PART NAMES AND FUNCTIONS

ES-M1 (Main unit)

ES-M2 (Expansion unit)

1. In N.O. operation mode: OFF-delay timer 10 ms

In N.C. operation mode: ON-delay timer 10 ms

I/O CIRCUIT DIAGRAM

WARNING

Sensor cable insertion port

Terminal block tightening screws

Mutual interference suppression selector switch

Operating indicator (Red)
Disconnection alarm indicator (Yellow)

Sensitivity adjustment trimmer

Output timer selector switch

1.

Output delay: 10 ms
Output timer OFF

Output mode selector switch

N.C. (NEAR-OFF)
N.O. (NEAR-ON)

Expansion
connector

FEATURES

One-line connection system

See “MOUNTING SEVERAL AMPLIFIERS” on page 2.

A wire-saving sensor system can be established by combining other
one-line connection amplifiers such as the FS-V10 Series or LV
Series.

Easy connection with the European terminal

See “SENSOR HEAD CONNECTION” on page 1.

The sensor head is connected to the amplifier through the European
terminal, allowing easy and quick connection.

Disconnection alarm indicator & output

See “PART NAMES AND FUNCTIONS” on page 1.

The alarm indicator and output turn on when the sensor head is
disconnected, enabling quick discovery of abnormal condition. (The
ES-M2 features the indicator only.)

Mutual interference suppression function

See “MUTUAL INTERFERENCE SUPPRESSION” on page 2.

Mutual interference among several sensors that are used in close
proximity can be suppressed by a simple operation.

ACCESSORIES

Instruction Manual: 1

End unit: 2 (ES-M2 only)

Metal screwdriver: 1

Cautions sticker: 1 (ES-M2 only)

Mounting bracket: 1 (ES-M1 only)

SENSOR HEAD CONNECTION

1. Modify the end of the sensor

cable as illustrated on the right.
Be sure to tightly twist the shield
wire and core wire separately.

* When the outer sheath is stripped, the shield wire appears around the core

wire. Separate the core wire and shield wire before modifying the cable.

2. Turn the terminal block tightening

screws counterclockwise to loosen
them.

3. Insert the sensor cable straight into

the insertion port of the amplifier.
Make sure that the core wire and
shield wire are inserted into the correct
ports and that the cable does not twist.

4. Turn the terminal block tightening

screws clockwise to tighten them. Be
sure to limit the tightening torque to
0.15 N•m.

5. Turn ON the amplifier and check that

the disconnection alarm indicator
remains OFF. If the indicator is ON, go
back to step 1 and repeat the
procedure again.

MOUNTING AMPLIFIER

Mounting/Detaching the amplifier to/from a DIN rail or
the mounting bracket

Hook the claw located at the amplifier cable side onto the DIN rail, and
then hook the front side claw to the rail while pressing the amplifier
forward. To detach the amplifier, unhook the front claw by lifting the
amplifier front side while pressing it forward.

Mounting

Detaching

Side mounting

Using the side holes of the supplied mounting bracket (ES-M1 only),
fix the amplifier with screws.

Outer sheath

Core wire

Shield wire

5

±

1 mm

14

±

1 mm

Terminal block
tightening screws

Shield wire

Core wire

Terminal block
tightening screws

M3 screw

ES-M1

PNP

NPN

ES-M1P

ES-M2

ES-M2P

(Control output)

(Control
output)

(Disconnection
alarm output)

(Disconnection
alarm output)

Main circuit

Overcurrent

protection circuit

Main circuit

Overcurrent

protection circuit

Main circuit

Overcurrent

protection circuit

Brown

Black

Load

Load

Load

Load

Orange

100mA max

100mA max

100mA max

Load

100mA max

100mA max

12 to 24 VDC

12 to 24 VDC

5 to 40 VDC

5 to 40 VDC

5 to 40 VDC

0V

OV

Blue

Brown

Black

(Control output)

Black

Orange

Blue

Main circuit

12 to 24 VDC

Black

(Control output)

Load

100mA max

OV

Overcurrent

protection circuit