7.7 Non-procedure Mode Programming
KV-300 Series Only
KV
-300
KV-10/80
Chapter 7 KV-L2 Serial Interface Module
1-292
7
7.7
Non-procedure Mode Programming
7.7.1
Operating in Non-procedure Mode
Communications protocol
In non-procedure mode, the KV-L2 can be connected to an external device having
an RS-232C or RS-422A terminal to write a series of text data (100 bytes maximum)
into data memory as a batch and to send text data from data memory to a connected
device.
Setting of the communications protocol and connection of the KV-L2 to an external
device are described below.
Setting the operation mode
Set the operation mode using the operation mode setting switch SET A (A1 to A4).
Use A1 and A2 to set the mode for port 1, and A3 and A4 to set the mode for port 2.
Turn OFF the power switch before setting the operation mode.
Set the operation mode setting switch A1 to A4 as above.
Setting the communications protocols
Set the baud rate, data bit length, parity, and stop bit with communications protocol
setting switch SET B (B1 to B8) according to the specifications of the external device
to be connected. Turn OFF the power switch before setting the switches.
ON
OFF
A1
A2
A3
A4
Operation mode
Port 1
Port 2
A1
A2
A3
A4
KV mode
OFF
OFF
OFF
OFF
Display Interface mode
OFF
ON
OFF
ON
Non-procedure mode
ON
ON
ON
ON
ON
OFF
B1
B2
B3
B4
B5
B6
B7
B8
B1
B2
B3
B4
B5
B6
B7
B8
Baud rate
1200 bits/s
OFF
OFF
OFF
OFF
2400 bits/s
ON
OFF
OFF
OFF
4800 bits/s
OFF
ON
OFF
OFF
9600 bits/s
ON
ON
OFF
OFF
19200 bits/s
OFF
OFF
ON
OFF
31250 bits/s
ON
OFF
ON
OFF
8400 bits/s
OFF
ON
ON
OFF
Setting disabled
ON
ON
ON
OFF
Parameters
Data bits
7 bits
OFF
OFF
8 bits
ON
OFF
Parity
None
OFF
OFF
OFF
Odd
ON
OFF
OFF
Even
ON
ON
OFF
Stop bit
1 bit
OFF
OFF
2 bits
ON
OFF
KVHKA Chap 07_5to10.p65
08.3.11, 11:18 AM
292