Rockwell Automation 2098-UWCPRG Ultraware Software User Manual User Manual
Page 293

Rockwell Automation Publication 2098-UM001G-EN-P - February 2011
295
Configuring the Kinetix 3 Drive Chapter 5
The Faults window has these commands.
Customize the Faults window for your Kinetix 3 drive by selecting one or more of
these commands:
•
Click Show Status to display or hide the Status pane.
•
Click Show Commands to display or hide the Commands pane.
•
Click Setup to open the window, where you can customize the status
display for this window.
•
Click Revert to return parameter settings to the values they held when you
opened this window.
E.108 E.CdFrE Position
Command
Frequency Error
Input frequency limit
exceeded
• Verify hardware type
selected in the drive
matches the physical
hardware.
• Change from open
collector to line drive.
• Reduce the speed
command.
• Apply gearing.
E.112 E.EStoP
Emergency Stop
Emergency stop (E-STOP)
signal detected
• Remove Emergency
stop conditions.
• Clear E-STOP.
E.11e E.IrAnG
Indexing Position Range
Overflow
The value of a Position
Parameter for indexing is
out of the range.
Use a value within the
range of -2,147,483,647
…2,147,483,647
E.114 E.ouCUr Motor
Phase
Over
Current
Problem with control or
main power circuitry if
this error occurs when
power is turned on.
Check wiring and power.
Excessive current to the
motor if this error occurs
during operation (current
more than 300% of the
rated current to the
motor more than 10 ms).
Check power, and set or
adjust the acceleration
and deceleration times.
Command Description
Fault History
Opens the Fault History window, where you can view a list of the
last 20 fault events that occurred since the drive was powered-up.
Clear Faults
Clears all drive faults.
Fault Detail
Opens the Fault Detail window.
Save Parameters
Saves the current working values as power-up values in memory
for the selected online drive and all of its children.
Status Description Possible Cause
Suggested Action