C.1.4 cia 402: standardised device profile area – Festo Электромотор MTR-DCI User Manual
Page 304

C. Reference – CANopen and CI objects
C-28
Festo P.BE-MTR-DCI-CO-EN en 1209a
C.1.4
CiA 402: Standardised Device Profile Area
Controlword CiA 402 (control word CiA 402)
CANopen / CI
6040h
– / 00h
Var
uint16
rw
Description
Modify the current controller status or trigger an activity. Status modifications
triggered by the control word must be read back via the status word. Only when
the requested status can be read, may a further command be written via the
control word. For a description of the state machine see section C.2. Values see
Tab. C/3. Specific features when accessing via CI see section C.3.4.
Bit
Value
Description
0
0x0001
Switch on
Control the status transitions.
These bits are evaluated together.
1
0x0002
Enable voltage
2
0x0004
Quick stop – low-active
3
0x0008
Enable operation
4
0x0010
Depends on operating mode (object 6060):
– Homing mode:
Start homing operation
– Profile position mode / torque mode: New setpoint (move to position)
5
0x0020
Depends on operating mode (object 6060h):
– Homing mode:
reserved (set to 0)
– Profile position mode: reserved (change_set_immediately not supported
in Record Select and Direct mode)
– Profile torque mode:
=1: with stroke limitation; =0: without stroke
=1:
limitation
6
0x0040
Depends on operating mode (object 6060h):
– Profile position mode: absolute / relative
– Homing mode:
reserved (set to 0)
– Profile torque mode:
reserved (set to 1)
7
0x0080
Reset fault
8
0x0100
Hold as per Hold option code – object 605Dh.
9
0x0200
reserved (= 0)
10
0x0400
reserved (= 0)
11
0x0800
Jog positive: Run as long as set
12
0x1000
Jog negative: Run as long as set
13
0x2000
Teach: Apply current value
14
0x4000
HMI Access locked
15
0x8000
Symmetrical ramp transfer via PDO, i.e. acceleration value also for braking. Not
when accessing via SDO or using the FCT.
Tab. C/3: Description of control word