Direct mode create readiness to operate, Commissioning 5-51 – Festo Электромотор MTR-DCI User Manual
Page 149

5. Commissioning
5-51
Festo P.BE-MTR-DCI-CO-EN en 1209a
2. Direct mode Create readiness to operate
2.1
Basic status of the drive when the supply voltage has
been switched on.
} Step 2.2 or 2.3
2.2
Disable device control by FCT/MMI.
Optionally, assuming of device control by the FCT/MMI
can be disabled with CCON.B5 = 1 (LOCK).
} Step 2.3
2.3
Enable drive. (Direct mode)
} Reference travel: Example 4, Tab. 5/11.
Step/
Description
Output data
Input data
Byte
B7 B6
B5 B4
B3 B2 B1
B0
Byte
B7 B6 B5 B4 B3 B2 B1 B0
2.1 Basic status
(device control HMI =
off )
Byte 1
OPM2 OPM1
LOCK
–
RESET BRAKE STOP
ENABL
E
Byte 1
OPM2 OPM1 LOCK
24VL
FAULT WARN OPEN ENABL
E
CCON
0
0
0
0
0
x
0
0
SCON
0
0
0
1
0
0
0
0
Byte 2
–
CLEAR TEACH JOGN
JOGP
HOM
START
HOLD
Byte 2
REF
STILL
DEV
MOV TEACH
MC
ACK
HOLD
CPOS
0
0
0
0
0
0
0
0
SPOS
0
0
0
0
0
1
0
0
2.2 Disable device
control by FCT/MMI
Byte 1
OPM2 OPM1
LOCK
–
RESET BRAKE STOP
ENABL
E
Byte 1
OPM2 OPM1 LOCK
24VL
FAULT WARN OPEN ENABL
E
CCON
x
x
1
0
x
x
x
x
SCON
x
x
0
x
x
x
x
x
Byte 2
–
CLEAR TEACH JOGN
JOGP
HOM
START
HOLD
Byte 2
REF
STILL
DEV
MOV TEACH
MC
ACK
HOLD
CPOS
0
x
x
x
x
x
x
x
SPOS
x
x
x
x
x
x
x
x
2.3 Enable drive, en-
able operation
(Direct mode)
Byte 1
OPM2 OPM1
LOCK
–
RESET BRAKE STOP
ENABL
E
Byte 1
OPM2 OPM1 LOCK
24VL
FAULT WARN OPEN ENABL
E
CCON
0
1
x
0
0
x
1
1
SCON
0
1
0
1
0
0
1
1
Byte 2
–
CLEAR TEACH JOGN
JOGP
HOM
START
HOLD
Byte 2
REF
STILL
DEV
MOV TEACH
MC
ACK
HOLD
CPOS
0
0
0
0
0
0
0
1
SPOS
0
0
0
0
0
1
0
1
0: 0-signal
1: 1-signal;
x: not relevant (optional);
F: Edge positive
Tab. 5/9: Control and status bytes “Create readiness to operate – Direct mode”
If there are faults after switching on or after setting CCON.B0
(ENABLE):
} Error treatment: see example 3, Tab. 5/10.