Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 60
Description of Features 4-33
1503-UM054C-EN-P – June 2013
Table 4.F - Plus Fault/Warning Description
Fault/Warning
Red LED
Green LED
Description
None
Off
Solid On
Application Firmware Running
None
Off
Flash @ 0.25Hz
Application Disable Jumper In
None
Off
Flash @ 0.50Hz
Programming Base Unit(s)
None
Off
Off
No power from IB or DeviceNet
Warning
Off
2 Pulses
RTC Fail
Warning
Off
3 Pulses
Line Undervoltage
Warning
Off
4 Pulses
Line Overvoltage
Warning
Off
5 Pulses
Extended Close Time (See Table 4.G)
Warning
Off
6 Pulses
DeviceNet Power Loss
(only if Power was available on power up
– need historical value)
Warning
Off
7 Pulses
MC Altitude Setting Warning
Fault
Solid On
Undefined
In RESET mode or F/W Crash
Fault
2 Pulses
Off
POST failure –RAM
Fault
5 Pulses
Off
Appl. Programming Error – CRC
Fault
6 Pulses
Off
RS485 Comm Fault (IB Fault)
Fault
7 Pulses
Off
IB1 Power Loss
Fault
8 Pulses
Off
Coil Open
Fault
9 Pluses
Off
System Lock Up
Table 4.F shows the operation of the Plus Status LED and the
faults/warnings that they indicate. This table makes use of two
methods of indicating a particular fault/warning.
The first method will flash the particular LED at a certain frequency
rate. Flashing at a rate of 0.25Hz, for example, means that the LED
will cycle from being off to on and to off again in 4 seconds, so that
it will be on for 2 seconds and off for 2 seconds. A flashing rate of
2.0Hz means that the LED will be on for 0.25 seconds and then off
for 0.25 seconds for a cycle time of 0.5 seconds.
The second method of indication is to flash a LED for a certain
number of pulses and then incorporate a pause in the cycle. The
pattern for a ‘2 Pulses’ pattern will be as follows:
1 – maintain LED on for 0.5 seconds
2 – maintain LED off for 0.5 seconds
3 – maintain LED on for 0.5 seconds
4 – maintain LED off for 0.5 seconds
5 – maintain LED off for 2 seconds
6 – repeat 1