Kltemperature, Pollution – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 18

1-8
Product Description
1503-UM054C-EN-P –June 2013
Through RSNetWorx, IntelliVAC Plus firmware version can be
viewed in device general page and base module version can be
viewed in parameter page.
Series C modules use only version 2.003 application firmware.
This firmware is also compatible with the Series A and B modules.
Series D modules use only version 3.001 or 3.002 application
firmware. This firmware is not compatible with any other Series
letter modules.
Series E modules use only 4.001 or newer
firmware. This firmware is not compatible with any other Series
Letter modules.
Refer to IntelliVAC manual 1503-UM053-EN-P for part numbers
of the various series of modules. The Series Letter of the module
is printed on the label on the cover of the module, beside the part
number.
Table 1.A – Mechanical Ratings
klTemperature
Operating: 0° to 60°C ambient at the control module
Non-Operating: -40° to 85°C
Altitude
-1000 to 5000 meters
Pollution
Pollution level II (as defined by UL 840 and IEC 60664-1)
Humidity
95% non-condensing
Shock and
Vibration
(Operational)
Shock – 15 g peak, 11 milliseconds
Vibration – 10 to 57 Hz, 0.015 inch displacement peak to peak
– 57 to 150 Hz, 2.5 g acceleration
Ambient temperature is derated at altitudes above 1,000 meters (3,300 feet).
Please refer to Table 1.C.