Devicenet macid – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 102

Communications 7-3
1503-UM054C-EN-P – June 2013
If AutoBaud is enabled then the DNet Baud that was selected will be
overridden with the baud rate detected on the network. If no network
activity is detected, then the baud rate will be set to the default baud
rate of 125k.
DeviceNet MACID
The address of the IntelliVAC Plus device shall be settable either
through DeviceNet or through the MACID rotary switches which are
accessible on the side of the IntelliVAC Plus enclosure. These rotary
switches allow an address range of 00 to 99 although only values of
00 to 63 are allowable.
Note:
The data read from the rotary switches must be inverted due
to the operation of the switches.
Rotary Switch
Figure 7.1 – Rotary Switch
Selection of the MACID will be as follows:
‘Set MACID = ‘ ‘00’ to ‘63’
The default MACID shall be set to ‘01’
The MACID setting can be viewed as follows:
‘MACID = ‘ ‘00’ to ‘63’
There shall be a DeviceNet parameter which will allow the MACID
to be set, either from DeviceNet or from the rotary switches. If the
rotary switches do not contain a valid address then the default
address will be used.
The MACID (read-only parameter) selection source setting will be as
follows:
‘MACID Source = ‘ ‘DNet’ or ‘Switches’ default is Dnet