Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 241
![background image](/manuals/578723/241/background.png)
B-66
Parameters
1503-UM054C-EN-P – June 2013
Table B.24 – Drop Out Time Settings from IB2 DIP Switches
Value
Enum Text
Description
0
50 ms
50 ms from IB2 DIP switches
1
75 ms
75 ms from IB2 DIP switches
2
100 ms
100 ms from IB2 DIP switches
3
130 ms
130 ms from IB2 DIP switches
4
150 ms
150 ms from IB2 DIP switches
5
175 ms
175 ms from IB2 DIP switches
6
200 ms
200 ms from IB2 DIP switches
7
240 ms
240 ms from IB2 DIP switches
Note:
The drop off time would be 6mS longer if the close command
is applied on IB.
Drop Out Time Setting From IB3 DIP Switches
[IB 3 Drop Out Time DIP Setting]
Parameter Number:
120,103,86,_,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-3-49
Group:
Configuration
Units:
see table
Minimum Value:
0
Maximum Value:
7
Default Value:
0
This parameter allows the user to view the Drop Out Time Setting
set from the IB3 DIP switches. The Drop Out Time is initially set by
the IB3 DIP switches but can be over-ridden by Parameter #115 after
which time the original IB3 DIP switch settings will no longer be
used.
Table B.25 – Drop Out Time Settings From IB3 DIP Switches
Value
Enum Text
Description
0
50 ms
50 ms from IB3 DIP switches
1
75 ms
75 ms from IB3 DIP switches
2
100 ms
100 ms from IB3 DIP switches
3
130 ms
130 ms from IB3 DIP switches
4
150 ms
150 ms from IB3 DIP switches
5
175 ms
175 ms from IB3 DIP switches
6
200 ms
200 ms from IB3 DIP switches
7
240 ms
240 ms from IB3 DIP switches
Note:
The drop off time would be 6 ms longer if the close command
is applied on IB.