Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 349

B-174
Parameters
1503-UM054C-EN-P – June 2013
Status Word for IB2 [IB 2 Status Word]
Parameter Number:
336,277,218,159,_.
Access rule:
Get
Data Type:
WORD
Object Mapping:
0x384-2-62
Group:
Diagnostics
Units:
-
Minimum Value:
0
Maximum Value:
0xFFFF
Default Value:
0
This parameter allows the user to view the IB2 Status Word.
If a bit
is ‘0’ then the fault or warning is not present. If a bit is a ‘1’ then the
fault or warning is present.
Table B.40 – Status Word for IB2
Bit
Enum Text
Description
0
Bit 0: unused
unused
1
Bit 1: unused
unused
2
Bit 2: unused
unused
3
Bit 3: Power Up with Contactors Closed
Power Up with Contactor Closed IB2
4
Bit 4: Open Coil Open
Trip Coil Open on IB2
5
Bit 5: Close Coil Open
Close Coil Open on IB2
6
Bit 6: Power Up with Invalid DIPs
Power Up with Invalid DIPs on IB2
7
Bit 7: MC Malfunction
MC Malfunction on IB2
8
Bit 8: Drop Out During Hold
Drop Out During Hold on IB2
9
Bit 9: Contactor Fails to Drop Out
Contactor Fails to Drop Out on IB2
10 Bit 10: Power Up with Close Command
Power Up with Close Command on IB2
11 Bit 11: Long Close Time
Long Close Time on IB2
12 Bit 12: Undervoltage with Close Command Present Undervoltage with Close Command Present on IB2
13 Bit 13: Long Drop Out Time
Long Drop Out Time on IB2
14 Bit 14: Mechanical Latch Trip Fail
Mechanical Latch Trip Fail on IB2
15 Bit 15: Invalid Command
Invalid Command on IB2