Parameters B-83
1503-UM054C-EN-P – June 2013
Jog Time for IB5 [IB 5 Jog Time]
Parameter Number:
152,_,_,_,_.
Access rule:
Get/Set
Data Type:
USINT
Object Mapping:
0x384-5-21
Group:
Configuration
Units:
Seconds
Minimum Value:
0
Maximum Value:
30
Default Value:
12
This parameter allows the user to view and set the Jog Time for
contactor IB5. It indicates the amount of time that a contactor can be
Jogged (momentarily closed) for. This is only for Electrically Held
contactors and makes use of the Open command. See Temporary
Jog Function in Chapter 4 for a more detailed description of this
feature.
Jog Repetition Time for IB1
[IB 1 Jog Repetition Time]
Parameter Number:
153,129,105,81,56.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-1-22
Group:
Configuration
Units:
Seconds
Minimum Value:
0
Maximum Value:
60
Default Value:
6
This parameter allows the user to view and set the Jog Repetition
Time for contactor IB1. It indicates the amount of time between
successive Jog intervals. Therefore, once a Jog interval has begun, it
cannot be repeated until the Jog Repetition Time has elapsed for
contactor IB1. This is only for Electrically Held contactors and
makes use of the Open command. See Temporary Jog Function in
Chapter 4 for a more detailed description of this feature.