E-10
DeviceNet Information
1503-UM054C-EN-P – June 2013
Table E.22 – Instance Attributes
Attribute
ID
Access Rule
Attribute Name
Data Type
Default
Value
Range
15
Get/Set
Autobaud Enable
BOOL
1
0=disabled
1=enabled
16
Get/Set
Consumed Assy
USINT
10
1~3
17
Get/Set
Produced Assy
USINT
1
10 ~ 13
19
Get/Set
Set To Defaults
BOOL
0
0=no action
1=reset
23
Get
I/O Produced Size
USINT
8
1~8
24
Get
I/O Consumed Size
USINT
5
1~5
64
Get/Set
Flash instance enable
UINT
0
110
Get/Set
PNB COS Mask
DWORD
0
0 … 0xFFFFFFFF
111
Get/Set
Status COS Mask ***
DWORD
0
0 … 0xFFFFFFFF
112
Get/Set
RTC Date
Date
0
1972-1-1 ~ 2151-6-6
113
Get/Set
RTC Time
Time
0
00:00:00.000
~
23:59:59.999
114
Get/Set
Preload DeviceLogix program
index
USINT
0
0~5
115
Get
Invalid DLX Program
USINT
0/1
0=invalid
1=valid
116
Get
Altitude
USINT
0
0: -1000~0000 M
1: 0001~1000 M
2: 1001~2000 M
3: 2001~3000 M
4: 3001~4000 M
5: 4001~5000 M
117
Get/Set
Time Zone
USINT
0
0~31 represent GMT-12
~ GMT+13 Hrs
118
Get/Set
Control Mask*
USINT
0-3
0=local
1=network
2=user customized
priority
119
Get/Set
Network command (Start,
stop, FWD, REV, Jog)
BYTE
0
Xx x00000- xxx11111
120
Get
Module Status
1: Test_Mode
2: Normal_Mode
3: Local_Mode
4: Remote_Mode
5: Isolation_SW
6: Speed_REV
7: Speed_FWD
8: Protection
BYTE
0
0-FF
121
Get
IB1 Status
BOOL
0
0=bad, IB power lost
1=good, IB power On
122
Get
MC altitude set warning
BOOL
0
1=Altitude Inconsistent
0=Not Fault
123
Get/Set
TDUV Time Source
BOOL
0
0=from IB
1=from IE
124
Get/Set
Drop Out Time Source
BOOL
0
0=from IB
1=from IE