Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 212

Parameters B-37
1503-UM054C-EN-P – June 2013
IntelliVAC Plus Action on Loss of DeviceNet Communications
[Loss Communication Action]
Parameter Number:
68,56,44,32,19.
Access rule:
Get/Set
Data Type:
BOOL
Object Mapping:
0xB4-1-125
Group:
Control
Units:
-
Minimum Value:
Hold
Maximum Value:
Reset
Default Value:
Hold
This parameter allows the user to view, as well as to select, the
control action which occurs after a loss of DeviceNet
communications occurs. There are two different actions that can be
selected, either Hold or Reset.
A detailed description for each of the Loss of Communications
Actions can be found in Chapter 7, DeviceNet Communications
Loss.
Control Bits Which Consumed on DeviceNet
[Consumed Net Work Bits]
Parameter Number:
69,57,45,33,20.
Access rule:
Get
Data Type:
WORD
Object Mapping:
0x4-3-3
Group:
Control
Units:
-
Minimum Value:
-
Maximum Value:
-
Default Value:
None
This parameter allows the user to view the status of the sixteen (16)
DeviceNet Consumed Network bits. Each bit position of the
parameter defines the state of one of the consumed network bits.
For each of the Consumed Network Bit’s listed, a status of ‘0’
indicates that the bit is disabled and a status of ‘1’ indicates that the
bit is enabled.