Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual

Page 27

background image

3-4

Installation

1503-UM054C-EN-P – June 2013

It is recommended the user interface with the IntelliVAC Plus using

interposing relays if possible. In the event that the IntelliVAC Plus

must be interfaced to a Solid State Output consult Table 3.A for

allowable leakage current values.

Table 3.A – Input Circuit Specifications





MOV

3

2

1

EC

-

+

4

TCO

12

11

AUX

CCO

5

6

L1

L2/N

G

+

-

STOP

START

OVERLOAD

CONTROL

POWER

FUSE

*

7

8

OPEN

16

15

CONTACTOR

STATUS

M

M-INTELLIVAC

M

CAPACITOR

(OPTIONA L)

+

-

9

10

CLOSE

14

13

MODULE

STATUS

CONTROL POWER

INPUT POWER

CONFIGURATION

DIP SWITCHES

Figure 3.3 – IntelliVAC Typical Schematic (Electrically Held Vacuum Contactor)

Command Inputs

AC – 70 to 240 V rms

DC – 70 to 250 V
Maximum on state current for input circuit:
11mA

AC

@ 276 V AC, 60Hz, T

A

= 60°C

2.4mA

DC

@ 276 V DC, T

A

= 60°C

Minimum on state current for input circuit:
2.5mA

AC

@ 74 V AC, 60Hz, T

A

= 60°C

1.2 mA @ 68 V DC, T

A

= 60°C

Maximum off state current for input circuit:
1.9 µA @ 20 V AC, 60 Hz, T

A

= 60°C

900 µA @ 60 V DC, T

A

= 60°C