Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 343
![background image](/manuals/578723/343/background.png)
B-168
Parameters
1503-UM054C-EN-P – June 2013
Invalid DeviceLogix Program Loaded
[Invalid DeviceLogix Program]
Parameter Number:
325,267,209,151,92.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0xB4-1-115
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Invalid DLX Prog.
Maximum Value:
1 = Valid or No DLX Prog.
Default Value:
1
This parameter allows the user to view the status of the DeviceLogix
Program that has been selected for operation. If the bit is a ‘0’ then
the DeviceLogix Program is invalid. This can occur if a Custom
DeviceLogix Program is loaded which has an incorrect setting that
would prevent the program from operating in a correct logical
manner. If the bit is a ‘1’ then the DeviceLogix Program selected is
either valid or is blank. A blank program could only occur if the
‘User customized DeviceLogix Prog.’ was selected as setting ‘0’ in
parameter #66, Preload DeviceLogix Program and the custom
program was blank.
Power Fail Status for IB1
[IB1 Power Fail Status]
Parameter Number:
326,268,210,152,93.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0xB4-1-121
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Bad
Maximum Value:
1 = Good
Default Value:
0
This parameter allows the user to view the status of the IB1 power
level. This refers to the +15VDC power supply on the IB unit which
powers the IE unit. If the bit is a ‘0’ then the IB1 power is bad. If
the bit is a ‘1’ then the IB1 power is good.