Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 179

B-4
Parameters
1503-UM054C-EN-P – June 2013
Auxiliary Input Status from IntelliVAC Base Unit #2
[IB 2 Module Aux. Status]
Parameter Number:
2,2,2,2,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-2-1
Group:
Control
Units:
-
Minimum Value:
0 = Closed
Maximum Value:
1 = Open
Default Value:
0
This parameter allows the user to view the status of the contactor
Auxiliary input from the IntelliVAC Basic Module #2. A Closed
status refers to the contactor Auxiliary input having no input voltage
which indicates that the contactor is Closed. An Open status refers
to the contactor Auxiliary input having a valid input voltage which
indicates that the contactor is Open. See the Electrical Specifications
section in Table 1.A for the voltage level for a valid Closed and
Open input.
Auxiliary Input Status from IntelliVAC Base Unit #3
[IB 3 Module Aux. Status]
Parameter Number:
3,3,3,_,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-3-1
Group:
Control
Units:
-
Minimum Value:
0 = Closed
Maximum Value:
1 = Open
Default Value:
0
This parameter allows the user to view the status of the contactor
Auxiliary input from the IntelliVAC Basic Module #3. A Closed
status refers to the contactor Auxiliary input having no input voltage
which indicates that the contactor is Closed. An Open status refers to
the contactor Auxiliary input having a valid input voltage which
indicates that the contactor is Open. See the Electrical Specifications
section in Table 1.A for the voltage level for a valid Closed and
Open input.