B-70
Parameters
1503-UM054C-EN-P – June 2013
Contactor Pick Up Time for IB5
[IB 5 Pick Up Time]
Parameter Number:
127,_,_,_,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-5-18
Group:
Configuration
Units:
mSeconds
Minimum Value:
0
Maximum Value:
255
Default Value:
0
This parameter allows the user to view the Pick Up Time for the IB5
contactor. The Pick Up Time is the interval from when a Close or
Trip command is issued to the time that the Contactor Auxiliary
contact on IB5 opens, indicating that the contactor is closed.
TDUV Time Setting from IB1 DIP Switches
[IB 1 TDUV Time DIP Setting]
Parameter Number:
128,109,90,71,51.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-1-58
Group:
Configuration
Units:
see table
Minimum Value:
0
Maximum Value:
3
Default Value:
0
This parameter allows the user to view the Time Delay Undervoltage
Setting set from the IB1 DIP switches. The Time Delay
Undervoltage Setting is initially set by the IB1 DIP switches but can
be over-ridden by Parameter #133 after which time the original IB1
DIP switch settings will no longer be used. See TDUV in Chapter 8
and Table 8.E.
Table B.28 – TDUV Time Setting From IB1 DIP Switches
Value
Enum Text
Description
0
0.2 Sec
0.2 Sec TDUV setting from IB1 DIP switches
1
0.5 Sec
0.5 Sec TDUV setting from IB1 DIP switches
2
1.0 Sec
1.0 Sec TDUV setting from IB1 DIP switches
3
2.0 Sec
2.0 Sec TDUV setting from IB1 DIP switches