Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 348
![background image](/manuals/578723/348/background.png)
Parameters B-173
1503-UM054C-EN-P – June 2013
Status Word for IB1 [IB 1 Status Word]
Parameter Number:
335,276,217,158,98.
Access rule:
Get
Data Type:
WORD
Object Mapping:
0x384-1-62
Group:
Diagnostics
Units:
-
Minimum Value:
0
Maximum Value:
0xFFFF
Default Value:
0
This parameter allows the user to view the IB1 Status Word.
If a bit
is ‘0’ then the fault or warning is not present. If a bit is a ‘1’ then the
fault or warning is present.
Table B.39 – Status Word for IB1
Bit
Enum Text
Description
0
Bit 0: unused
unused
1
Bit 1: unused
unused
2
Bit 2: unused
unused
3
Bit 3: Power Up with Contactors Closed
Power Up with Contactor Closed IB1
4
Bit 4: Open Coil Open
Trip Coil Open on IB1
5
Bit 5: Close Coil Open
Close Coil Open on IB1
6
Bit 6: Power Up with Invalid DIPs
Power Up with Invalid DIPs on IB1
7
Bit 7: MC Malfunction
MC Malfunction on IB1
8
Bit 8: Drop Out During Hold
Drop Out During Hold on IB1
9
Bit 9: Contactor Fails to Drop Out
Contactor Fails to Drop Out on IB1
10
Bit 10: Power Up with Close Command
Power Up with Close Command on IB1
11
Bit 11: Long Close Time
Long Close Time on IB1
12
Bit 12: Undervoltage with Close Command Present
Undervoltage with Close Command Present on IB1
13
Bit 13: Long Drop Out Time
Long Drop Out Time on IB1
14
Bit 14: Mechanical Latch Trip Fail
Mechanical Latch Trip Fail on IB1
15
Bit 15: Invalid Command
Invalid Command on IB1