Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 234
Parameters B-59
1503-UM054C-EN-P – June 2013
Power-Up Safety Setting for IB4
[IB 4 Power-Up Safety Setting]
Parameter Number:
106,92,_,_,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-4-16
Group:
Configuration
Units:
-
Minimum Value:
0 = Enable
Maximum Value:
1 = Disable
Default Value:
0
This parameter allows the user to view the status of the Power-Up
Safety setting for the IB4 module. If it is enabled then the IB4
contactor will not close the contactor if the unit powers up with a
Close command present. If it is disabled then the IB4 contactor will
close the contactor if the unit powers up with a Close command
present. See Power-up Safety in Chapter 8 and Table 8.F.
Power-Up Safety Setting for IB5
[IB 5 Power-Up Safety Setting]
Parameter Number:
107,_,_,_,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-5-16
Group:
Configuration
Units:
-
Minimum Value:
0 = Enable
Maximum Value:
1 = Disable
Default Value:
0
This parameter allows the user to view the status of the Power-Up
Safety setting for the IB5 module. If it is enabled then the IB5
contactor will not close the contactor if the unit powers up with a
Close command present. If it is disabled then the IB5 contactor will
close the contactor if the unit powers up with a Close command
present. See Power-up Safety in Chapter 8 and Table 8.F.