B-58
Parameters
1503-UM054C-EN-P – June 2013
Power-Up Safety Setting for IB2
[IB 2 Power-Up Safety Setting]
Parameter Number:
104,90,76,62,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-2-16
Group:
Configuration
Units:
-
Minimum Value:
0 = Enable
Maximum Value:
1 = Disable
Default Value:
0
This parameter allows the user to view the status of the Power-Up
Safety setting for the IB2 module. If it is enabled then the IB2
contactor will not close the contactor if the unit powers up with a
Close command present. If it is disabled then the IB2 contactor will
close the contactor if the unit powers up with a Close command
present. See Power-up Safety in Chapter 8 and Table 8.F.
Power-Up Safety Setting for IB3
[IB 3 Power-Up Safety Setting]
Parameter Number:
105,91,77,_,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-3-16
Group:
Configuration
Units:
-
Minimum Value:
0 = Enable
Maximum Value:
1 = Disable
Default Value:
0
This parameter allows the user to view the status of the Power-Up
Safety setting for the IB3 module. If it is enabled then the IB3
contactor will not close the contactor if the unit powers up with a
Close command present. If it is disabled then the IB3 contactor will
close the contactor if the unit powers up with a Close command
present. See Power-up Safety in Chapter 8 and Table 8.F.