Delay Restart Time for IB5
[IB 5 Delay Restart Time]
Parameter Number:
142,_,_,_,_.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-5-19
Group:
Configuration
Units:
Seconds
Minimum Value:
6
Maximum Value:
3600
Default Value:
12
This parameter allows the user to view and set the Delay Restart
Time between successive Open/Trip and Close commands for
contactor IB5. This sets a maximum repetition time for the cycling
of the contactor. It can also be used to prevent rapid restating of the
motor. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.