Ib faults / warnings, Healthy module and contactor open – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 50
Description of Features 4-23
1503-UM054C-EN-P – June 2013
Table 4.E – IB Fault/Warning Descriptions
IntelliVAC Status Indication (Series E only)
Conditions
Description
Module Status
Contactor Status
LED Color
Relay
LED Color
Relay
Normal
Healthy Module and Contactor OPEN
Green
Closed
Off
Open
Normal
Healthy Module and Contactor CLOSED
Green
Closed
Yellow
Closed
Warning
Invalid Command Present
12
Yellow
Closed
Off
Open
Warning
Mechanical Latch Fail to Trip
Yellow
Closed
Yellow
Closed
Fault
Power Up with Contactor CLOSED
Red – Flash 2
Open
Yellow
Closed
Warning
Contactor Fails to Pick Up
Yellow – R1
Closed
Off / Yellow
Open/Closed
Warning
Contactor Drop Out During Hold
Yellow – R2
Closed
Off / Yellow
Open/Closed
Warning
Long Contactor Drop Out Time
Yellow – R3
Closed
Off / Yellow
Open/Closed
Fault
Microcontroller Malfunction
Red
Open
Red
Open
Fault
Power Up with Invalid DIP Switch Configuration
Red – Flash 1
Open
Off
Open
Fault
Contactor Fails to Drop Out
Red – Flash 3
Open
Red
Open
Fault
RS485 Communications Error
Red – Flash 4
Open
Off
Open
Warning
Undervoltage with a CLOSE Command Present
Yellow – Flashing Open/Closed Off / Yellow
Open/Closed
Warnings will be cleared when a change of input state occurs, and the condition has been resolved.
Faults require control power to be removed until the unit resets
Flash 1 = 1 Flash Red LED followed by a pause
Flash 2 = 2 Consecutive Red LED flashes followed by a pause
Flash 3 = 3 Consecutive Red LED flashes followed by a pause
Flash 4 = 4 Consecutive Red LED flashes followed by a pause
Yellow – R1 = Yellow with 1 Red flash followed by a pause
Yellow – R2 = Yellow with 2 consecutive Red flashes followed by a pause
Yellow – R3 = Yellow with 3 consecutive Red flashes followed by a pause
Open during undervoltage, Closed if voltage restored
Will reflect actual status of the contactor
12
Invalid Command Types:
1. Close, Jog or Trip commands present during power up sequence
2. Close or Jog command re-applied too quickly (before contactor opening sequence is verified).
Allow at least 60 msec, plus drop out delay time, before re-applying these signals.
NOTE: Contactor will only respond to a close command re-applications after the re-start delay timer has expired.
3. Close and Trip commands present simultaneously (valid with Mechanical Latch contactors only).
IB Faults / Warnings
Healthy Module and Contactor OPEN
This is a Normal condition and no additional action is required.
This indicates that the Basic module within the IntelliVAC Plus unit
has no faults or warnings and the status of the contactor being
controlled is in an Open condition.
The Module status LED is Green to indicate a good module and the
Module status relay is closed to allow externally connected circuits
to function.