Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 181
![background image](/manuals/578723/181/background.png)
B-6
Parameters
1503-UM054C-EN-P – June 2013
Close Input Status from IntelliVAC Base Unit #1
[IB 1 Module Close Status]
Parameter Number:
6,5,4,3,2.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-1-2
Group:
Control
Units:
-
Minimum Value:
0 = Off
Maximum Value:
1 = On
Default Value:
0
This parameter allows the user to view the status of the contactor
Close input from the IntelliVAC Basic Module #1. An Off status
refers to the Close input having no input voltage indicating an
absence of a Close input. An On status refers to the Close input
having a valid input voltage indicating a presence of a Close input.
See the Electrical Specifications section in Table 1.A for the voltage
level for a valid Off and On input.
Close Input Status from IntelliVAC Base Unit #2
[IB 2 Module Close Status]
Parameter Number:
7,6,5,4,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-2-2
Group:
Control
Units:
-
Minimum Value:
0 = Off
Maximum Value:
1 = On
Default Value:
0
This parameter allows the user to view the status of the contactor
Close input from the IntelliVAC Basic Module #2. An Off status
refers to the Close input having no input voltage indicating an
absence of a Close input. An On status refers to the Close input
having a valid input voltage indicating a presence of a Close input.
See the Electrical Specifications section in Table 1.A for the voltage
level for a valid Off and On input.