Net out9/speed sw fwd status, Net out 10/speed sw rev status, Net out 11/isolation sw status – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 159: Net out 12/remode mode status, Net out 13/local mode status, Net out 14/ normal mode status, Net out 15/test mode status, Net out 16, 18, 20, 22, 24/ ibx trip coil, Net out 17, 19, 21, 23, 25/ ibx close coil, Net out 26/stop status

9-36
DeviceLogix
1503-UM054C-EN-P – June 2013
Net Out9/Speed SW FWD Status
This is the output portion of the Speed SW FWD Status dual
function bit.
Net out 10/Speed SW REV Status
This is the output portion of the Speed SW REV Status dual function bit.
Net Out 11/Isolation SW status
This is the output portion of the Isolation SW status dual function bit.
Net Out 12/Remode Mode Status
This is the output portion of the Remote Mode Status dual function bit.
Net Out 13/Local Mode Status
This is the output portion of the Local Mode Status dual function bit.
Net out 14/ Normal Mode Status
This is the output portion of the Normal Mode Status dual function bit.
Net Out 15/Test Mode Status
This is the output portion of the Test Mode Status dual function bit
Net out 16, 18, 20, 22, 24/ IBX Trip Coil
These bits represent the “Trip” or “Open” coil for a mechanically
latched contactor. Setting this bit will result in opening a
mechanically latched contactor.
Net Out 17, 19, 21, 23, 25/ IBX Close coil
These bits represent the “Close” coil for both the mechanically
latched and electrically held contactors. For an electrically held
contactor the contactor is closed when the bit is set, and opens when
the bet is reset. For a mechanically latched contactor the bit is
pulsed to close the contactor and does not require to be maintained
set for the contactor to remain closed.
Net Out 26/Stop Status
This is the output portion of the “Stop Status” dual function bit.
Net Out 27/Start