Type of Contactor Selected for IB2 [IB 2 Contactor Type]

Parameter Number:

94,82,70,58,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-2-14

Group:

Configuration

Units:

-

Minimum Value:

0

Maximum Value:

3

Default Value:

0

This parameter allows the user to view the status of the type of

contactor that is being controlled by the IB2 module. This value is

set by the DIP switches on the IB2 module only (see Table 8.C).

Table B.19 – Type of Contactor for IB2 Unit

Value

Enum Text

Description

0

400A Mech. Latch

IB2 is a 400A Mechanically Latched contactor

1

400A Elec. Held

IB2 is a 400A Electrically Held contactor

2

800A Mech. Latch

IB2 is an 800A Mechanically Latched contactor

3

800A Elec. Held

IB2 is an 800A Electrically Held contactor


Type of Contactor Selected for IB3 [IB 3 Contactor Type]

Parameter Number:

95,83,71,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-3-14

Group:

Configuration

Units:

-

Minimum Value:

0

Maximum Value:

3

Default Value:

0

This parameter allows the user to view the status of the type of

contactor that is being controlled by the IB3 module. This value is

set by the DIP switches on the IB3 module only (see Table 8.C).

Table B.20 – Type of Contactor for IB3 Unit

Value

Enum Text

Description

0

400A Mech. Latch

IB3 is a 400A Mechanically Latched contactor

1

400A Elec. Held

IB3 is a 400A Electrically Held contactor

2

800A Mech. Latch

IB3 is an 800A Mechanically Latched contactor

3

800A Elec. Held

IB3 is an 800A Electrically Held contactor