Parameters B-69

1503-UM054C-EN-P – June 2013


Contactor Pick Up Time for IB3
[IB 3 Pick Up Time]
Parameter Number:

125,107,89,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-3-18

Group:

Configuration

Units:

mSeconds

Minimum Value:

0

Maximum Value:

255

Default Value:

0

This parameter allows the user to view the Pick Up Time for the IB3

contactor. The Pick Up Time is the interval from when a Close or

Trip command is issued to the time that the Contactor Auxiliary

contact on IB3 opens, indicating that the contactor is closed.


Contactor Pick Up Time for IB4
[IB 4 Pick Up Time]

Parameter Number:

126,108,_,_,_.

Access rule:

Get

Data Type:

USINT

Object Mapping:

0x384-4-18

Group:

Configuration

Units:

mSeconds

Minimum Value:

0

Maximum Value:

255

Default Value:

0

This parameter allows the user to view the Pick Up Time for the IB4

contactor. The Pick Up Time is the interval from when a Close or

Trip command is issued to the time that the Contactor Auxiliary

contact on IB4 opens, indicating that the contactor is closed.