Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 246
![background image](/manuals/578723/246/background.png)
Parameters B-71
1503-UM054C-EN-P – June 2013
TDUV Time Setting from IB2 DIP Switches
[IB 2 TDUV Time DIP Setting]
Parameter Number:
129,110,91,72,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-2-58
Group:
Configuration
Units:
see table
Minimum Value:
0
Maximum Value:
3
Default Value:
0
This parameter allows the user to view the Time Delay Undervoltage
Setting set from the IB2 DIP switches. The Time Delay
Undervoltage Setting is initially set by the IB2 DIP switches but can
be over-ridden by Parameter #134 after which time the original IB2
DIP switch settings will no longer be used. See TDUV in Chapter 8
and Table 8.E.
Table B.29 – TDUV Time Setting From IB2 DIP Switches
Value
Enum Text
Description
0
0.2 Sec
0.2 Sec TDUV setting from IB2 DIP switches
1
0.5 Sec
0.5 Sec TDUV setting from IB2 DIP switches
2
1.0 Sec
1.0 Sec TDUV setting from IB2 DIP switches
3
2.0 Sec
2.0 Sec TDUV setting from IB2 DIP switches
TDUV Time Setting from IB3 DIP Switches
[IB 3 TDUV Time DIP Setting]
Parameter Number:
130,111,92,_,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-3-58
Group:
Configuration
Units:
see table
Minimum Value:
0
Maximum Value:
3
Default Value:
0
This parameter allows the user to view the Time Delay Undervoltage
Setting set from the IB3 DIP switches. The Time Delay
Undervoltage Setting is initially set by the IB3 DIP switches but can
be over-ridden by Parameter #135 after which time the original IB3
DIP switch settings will no longer be used. See TDUV in Chapter 8
and Table 8.E.