Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 377
E-12
DeviceNet Information
1503-UM054C-EN-P – June 2013
Table E.25 - Instance Attribute
Parameter
No.
Control Parameter
Access
Rule
Type
Description
NV
CCV
1
AUX Status
Get
BOOL
1=open
0=close
N
N
2
CLOSE Status
Get
BOOL
0=not present
1=present
N
N
3
OPEN Status
Get
BOOL
0=not present
1=present
N
N
4
Close Coil Command
Get/Set
BOOL
1=Open
0=Close
N
N
5
Trip Coil Command
Get/Set
BOOL
1=Close
0=Open
N
N
6
Contactor Relay Status
Get
BOOL
0=open
1=close
N
N
7
Module Relay Status
Get
BOOL
0=open
1=close
N
N
8
Close Current
Get
LONG INT* 0~xx.xxx A
N
N
9
Hold Current
Get
LONG INT* 0~xx .xxx A
N
N
10
Trip Current
Get
LONG INT* 0~xx.xxx A
N
N
11
Line Voltage
Get
LONG INT* 0~xx.xxx V
N
N
12
DC Bus Voltage
Get
LONG INT* 0~xx.xxx V
N
N
13
Drop-out Time
(from IB or IE)
Get/Set
USINT
50~240 ms
Y
Y
14
Contactor Type (from IB)
Get
USINT
0=400A Mech. Latch
1=400A Elec. Held
2=800A Mech. Latch
3=800A Elec. Held
4~F=TBD
N
N
15
TDUV Config (from IB)
Get/Set
BOOL
0=disable
1=enable
Y
Y
16
Power-up Safety (from IB or IE)
Get
BOOL
0=enable
1=disable
N
N
17
Learn Mode (from IB)
Get
BOOL
0=Off
1=On
N
N
18
Pick-up Time
Get
USINT
0~255 ms
N
N
19
Delay Restart Time
Get/Set
UINT
6(12) ~ 3600 Sec
Y
Y
20
Delay Restart Wait Time
Get
UINT
0 ~ 3600 Sec
N
N
21
Jog Time
Get/Set
USINT
0 ~ 30 Sec, default
12
Y
Y
22
Jog Repetition Time
Get/Set
UINT*
0 ~ 60 second,
default 6
Y
Y
23
IB Invalid Command
Get
BOOL
0=not present
1=present
N
N
24
IB Mechanical Latch Fail to Trip
Get
BOOL
0=not present
1=present
N
N
25
Contactor Fails to Pick-Up
Get
BOOL
0=not present
1=present
N
N
26
Contactor Drop-out during Hold
Get
BOOL
0=not present
1=present
N
N
27
Contactor Fails To Drop Out
Get
BOOL
0=not present
1=present
N
N
28
IB Module Not Healthy
Get
BOOL
0=not healthy
1=healthy
N
N
29
Power-up with Contactor Closed
Get
BOOL
0=not present
1=present
N
N
30
Power-up with Invalid DIP
Switch Configuration
Get
BOOL
0=not present
1=present
N
N