Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 252

Parameters B-77
1503-UM054C-EN-P – June 2013
Delay Restart Time for IB3
[IB 3 Delay Restart Time]
Parameter Number:
140,119,98,_,_.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-3-19
Group:
Configuration
Units:
Seconds
Minimum Value:
6
Maximum Value:
3600
Default Value:
12
This parameter allows the user to view and set the Delay Restart
Time between successive Open/Trip and Close commands for
contactor IB3. This sets a maximum repetition time for the cycling
of the contactor. It can also be used to prevent rapid restating of the
motor. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.
Delay Restart Time for IB4
[IB 4 Delay Restart Time]
Parameter Number:
141,120,_,_,_.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-4-19
Group:
Configuration
Units:
Seconds
Minimum Value:
6
Maximum Value:
3600
Default Value:
12
This parameter allows the user to view and set the Delay Restart
Time between successive Open/Trip and Close commands for
contactor IB4. This sets a maximum repetition time for the cycling
of the contactor. It can also be used to prevent rapid restating of the
motor. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.