Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 237

B-62
Parameters
1503-UM054C-EN-P – June 2013
Learn Mode Setting From IB5
[IB 5 Learn Mode Setting]
Parameter Number:
112,_,_,_,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-5-17
Group:
Configuration
Units:
-
Minimum Value:
0 = Off
Maximum Value:
1 = On
Default Value:
0
This parameter allows the user to view the status of the Learn Mode
setting for the IB5 module. If it is Off, then the IB5 contactor will
not try to determine the type of contactor that it is connected to. If it
is On, then the IB5 contactor will try to determine the type of
contactor that it is connected to. This feature is not functional on the
Rev 1.01 firmware release
.
Drop Out Time Setting for IB1
[IB 1 Drop Out Time]
Parameter Number:
113,97,81,65,48.
Access rule:
Get/Set
Data Type:
USINT
Object Mapping:
0x384-1-13
Group:
Configuration
Units:
milliseconds
Minimum Value:
50
Maximum Value:
240
Default Value:
50
This parameter allows the user to view and set the Drop Out Time
setting for the IB1 module. The Drop Out Time is the time required
from the moment that an Open or Trip command is issued to the time
that the Contactor Auxiliary Status contact, on IB1, closes, to
indicate that the contactor has opened. See Contactor Drop Out
Time in Chapter 8 and Table 8.B.