Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 354

Parameters B-179
1503-UM054C-EN-P – June 2013
Termination Resistor Installed in IB3
[IB3 Termination Resistor]
Parameter Number:
342,282,222,_,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-3-63
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of the MC
Termination Resistor installation on IB3. If this bit is ‘0’, then the
MC Termination Resistor is not installed on the IB3 unit. If this bit
is ‘1’, then the MC Termination Resistor is installed on the IB3 unit.
For the MC system to have the correct Termination Resistor installed,
only the last MC unit in the MC system must have its resistor turned
on.
Termination Resistor Installed in IB4
[IB4 Termination Resistor]
Parameter Number:
343,282,_,_,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-4-63
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of the MC
Termination Resistor installation on IB4. If this bit is ‘0’, then the
MC Termination Resistor is not installed on the IB4 unit. If this bit
is ‘1’, then the MC Termination Resistor is installed on the IB4 unit.
For the MC system to have the correct Termination Resistor installed,
only the last MC unit in the MC system must have its resistor turned
on.