Intellivac base module object – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 376

DeviceNet Information E-11
1503-UM054C-EN-P – June 2013
Table E.22 – Instance Attributes (cont.)
Attribute
ID
Access Rule
Attribute Name
Data Type
Default
Value
Range
125
Get/Set
Communication Loss Action
BOOL
0
0=Hold
1=RESET
detail
126
Get
Ready Status
BOOL
0
0=FALSE
1=TRUE
127
Get/Set
MC System Status
UINT
0
128
Get/Set
IE status word
UINT
0
129
Get
Running status
BOOL
0
0=FALSE
1=TRUE
130
Get
System locked
BOOL
0
0=not active
1=active
131
Get/Set
Reset All
BOOL
0
0=no action
1=reset all fault and
warning
Note *:
1. The Setting of Mask is only could be done in specific condition.
The setting of Customize priority is only could be done in specific condition if Mask=2
Note**:
some bits are set to clear fault/warning
Note***:
the status is: Byte 0, IE inputs, assembly 10, byte 0
Byte 1~2: IB inputs, assembly 10, byte 5~6
Byte 3; Status, assembly 10, byte 4
Table E.23 - Common Services
Service Code
Implementation for
Service Name
Class
Instance
0E hex
Yes
Yes
Get_Attribute_Single
10 hex
No
Yes
Set_Attribute_Single
IntelliVAC Base Module Object
This is a vendor specific class defined for IntelliVAC base module.
Table E.24 - Class Attributes
Attribute ID
Access Rule
Name
DeviceNet
Data Type
Data Value
1
Get
Revision
UINT
1
2
Get
Max instance
UINT
1~5, depends on the product option
Number of Instances
: 1~5, depends on the IB number