Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 232
Parameters B-57
1503-UM054C-EN-P – June 2013
Time Delay UnderVoltage Setting for IB5
[IB 5 TDUV Configure]
Parameter Number:
102,_,_,_,_.
Access rule:
Get/Set
Data Type:
BOOL
Object Mapping:
0x384-5-15
Group:
Configuration
Units:
-
Minimum Value:
0 = Disable
Maximum Value:
1 = Enable
Default Value:
0
This parameter allows the user to view and set the status of the Time
Delay UnderVoltage setting for the IB5 contactor module. If it is
disabled then the TDUV feature for the IB5 contactor is disabled. If
it is enabled then the TDUV feature for the IB5 contactor is enabled.
See TDUV in Chapter 8 and Table 8.D.
Power-Up Safety Setting for IB1
[IB 1 Power-Up Safety Setting]
Parameter Number:
103,89,75,61,46.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-1-16
Group:
Configuration
Units:
-
Minimum Value:
0 = Enable
Maximum Value:
1 = Disable
Default Value:
0
This parameter allows the user to view the status of the Power-Up
Safety setting for the IB1 module. If it is enabled then the IB1
contactor will not close the contactor if the unit powers up with a
Close command present. If it is disabled then the IB1 contactor will
close the contactor if the unit powers up with a Close command
present. See Power-up Safety in Chapter 8 and Table 8.F.