B-80
Parameters
1503-UM054C-EN-P – June 2013
Delay Restart Wait Time for IB4
[IB 4 Delay Restart Wait Time]
Parameter Number:
146,124,_,_,_.
Access rule:
Get
Data Type:
UINT
Object Mapping:
0x384-4-20
Group:
Configuration
Units:
Seconds
Minimum Value:
0
Maximum Value:
3600
Default Value:
0
This parameter allows the user to view the Delay Restart Wait Time
for IB4. It shows the time left, as a constantly updated real time,
after the contactor has closed, before it is permitted to close again.
This parameter works in conjunction with parameter #141 which
defines the minimum time allowed between successive closings of
contactor IB4. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.
Delay Restart Wait Time for IB5
[IB 5 Delay Restart Wait Time]
Parameter Number:
147,_,_,_,_.
Access rule:
Get
Data Type:
UINT
Object Mapping:
0x384-5-20
Group:
Configuration
Units:
Seconds
Minimum Value:
0
Maximum Value:
3600
Default Value:
0
This parameter allows the user to view the Delay Restart Wait Time
for IB5. It shows the time left, as a constantly updated real time,
after the contactor has closed, before it is permitted to close again.
This parameter works in conjunction with parameter #142 which
defines the minimum time allowed between successive closings of
contactor IB5. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.