Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 298

Parameters B-123
1503-UM054C-EN-P – June 2013
Loss of Input Line Power on IB2 [IB 2 Line Loss]
Parameter Number:
234,194,154,114,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-2-47
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of Loss of Input Line
Power fault from the IB2 module. If the bit is ‘0’ then the warning is
not present. If the bit is ‘1’ then the warning is present. See Supply
Voltage in Chapter 4 for a detailed description of this warning.
Loss of Input Line Power on IB3 [IB 3 Line Loss]
Parameter Number:
235,195,155,_,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-3-47
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of Loss of Input Line
Power fault from the IB3 module. If the bit is ‘0’ then the warning is
not present. If the bit is ‘1’ then the warning is present. See Supply
Voltage in Chapter 4 for a detailed description of this warning.
Loss of Input Line Power on IB4 [IB 4 Line Loss]
Parameter Number:
236,196,_,_,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-4-47
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of Loss of Input Line
Power fault from the IB4 module. If the bit is ‘0’ then the warning is
not present. If the bit is ‘1’ then the warning is present. See Supply
Voltage in Chapter 4 for a detailed description of this warning.