Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 251

B-76
Parameters
1503-UM054C-EN-P – June 2013
Delay Restart Time for IB1
[IB 1 Delay Restart Time]
Parameter Number:
138,117,96,75,53.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-1-19
Group:
Configuration
Units:
Seconds
Minimum Value:
6
Maximum Value:
3600
Default Value:
12
This parameter allows the user to view and set the Delay Restart
Time between successive Open/Trip and Close commands for
contactor IB1. This sets a maximum repetition time for the cycling
of the contactor. It can also be used to prevent rapid restating of the
motor. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.
Delay Restart Time for IB2
[IB 2 Delay Restart Time]
Parameter Number:
139,118,97,76,_.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-2-19
Group:
Configuration
Units:
Seconds
Minimum Value:
6
Maximum Value:
3600
Default Value:
12
This parameter allows the user to view and set the Delay Restart
Time between successive Open/Trip and Close commands for
contactor IB2. This sets a maximum repetition time for the cycling
of the contactor. It can also be used to prevent rapid restating of the
motor. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.