Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 239
![background image](/manuals/578723/239/background.png)
B-64
Parameters
1503-UM054C-EN-P – June 2013
Drop Out Time Setting for IB4
[IB 4 Drop Out Time]
Parameter Number:
116,100,_,_,_.
Access rule:
Get/Set
Data Type:
USINT
Object Mapping:
0x384-4-13
Group:
Configuration
Units:
milliseconds
Minimum Value:
50
Maximum Value:
240
Default Value:
50
This parameter allows the user to view and set the Drop Out Time
setting for the IB4 module. The Drop Out Time is the time required
from the moment that an Open or Trip command is issued to the time
that the Contactor Auxiliary Status contact, on IB4, closes, to
indicate that the contactor has opened. See Contactor Drop Out
Time in Chapter 8 and Table 8.B.
Drop Out Time Setting for IB5
[IB 5 Drop Out Time]
Parameter Number:
117,_,_,_,_.
Access rule:
Get/Set
Data Type:
USINT
Object Mapping:
0x384-5-13
Group:
Configuration
Units:
milliseconds
Minimum Value:
50
Maximum Value:
240
Default Value:
50
This parameter allows the user to view and set the Drop Out Time
setting for the IB5 module. The Drop Out Time is the time required
from the moment that an Open or Trip command is issued to the time
that the Contactor Auxiliary Status contact, on IB5, closes, to
indicate that the contactor has opened. See Contactor Drop Out
Time in Chapter 8 and Table 8.B.