Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 243

B-68
Parameters
1503-UM054C-EN-P – June 2013
Table B.27 – Drop Out Time Settings From IB5 DIP Switches
Value
Enum Text
Description
0
50 ms
50 ms from IB5 DIP switches
1
75 ms
75 ms from IB5 DIP switches
2
100 ms
100 ms from IB5 DIP switches
3
130 ms
130 ms from IB5 DIP switches
4
150 ms
150 ms from IB5 DIP switches
5
175 ms
175 ms from IB5 DIP switches
6
200 ms
200 ms from IB5 DIP switches
7
240 ms
240 ms from IB5 DIP switches
Contactor Pick Up Time for IB1
[IB 1 Pick Up Time]
Parameter Number:
123,105,87,69,50.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-1-18
Group:
Configuration
Units:
mSeconds
Minimum Value:
0
Maximum Value:
255
Default Value:
0
This parameter allows the user to view the Pick Up Time for the IB1
contactor. The Pick Up Time is the interval from when a Close or
Trip command is issued to the time that the Contactor Auxiliary
contact on IB1 opens, indicating that the contactor is closed.
Contactor Pick Up Time for IB2
[IB 2 Pick Up Time]
Parameter Number:
124,106,88,70,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-2-18
Group:
Configuration
Units:
mSeconds
Minimum Value:
0
Maximum Value:
255
Default Value:
0
This parameter allows the user to view the Pick Up Time for the IB2
contactor. The Pick-Up Time is the interval from when a Close or
Trip command is issued to the time that the Contactor Auxiliary
contact on IB2 opens, indicating that the contactor is closed.