Parameters B-75
1503-UM054C-EN-P – June 2013
TDUV Time Setting for IB4
[IB 4 TDUV Time]
Parameter Number:
136,116,_,_,_.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-4-50
Group:
Configuration
Units:
Seconds error in EDS file
Minimum Value:
0.2
Maximum Value:
2.0
Default Value:
0.2
This parameter allows the user to view and set the Time Delay
Undervoltage setting for the IB4 module. The Time Delay
Undervoltage setting is the time allowed for contactor IB4 to remain
operational when the mains input voltage goes below the minimum
operating voltage (see Electrical Specifications section for both
Close and Hold modes). See TDUV Programmability in Chapter 4
for a detailed description of this feature.
TDUV Time Setting for IB5
[IB 5 TDUV Time]
Parameter Number:
137,_,_,_,_.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-5-50
Group:
Configuration
Units:
Seconds error in EDS file
Minimum Value:
0.2
Maximum Value:
2.0
Default Value:
0.2
This parameter allows the user to view and set the Time Delay
Undervoltage setting for the IB5 module. The Time Delay
Undervoltage setting is the time allowed for contactor IB5 to remain
operational when the mains input voltage goes below the minimum
operating voltage (see Electrical Specifications section for both
Close and Hold modes). See TDUV Programmability in Chapter 4
for a detailed description of this feature.