Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 132
DeviceLogix 9-9
1503-UM054C-EN-P – June 2013
1. Upload Logic
To upload logic click the Upload Logic icon or alternatively
select Communications> Upload. The logic configuration in
the device is read and displayed in the Function Block Editor.
Any unsaved changes will be discarded and Online Animation
Begins.
When you upload, the uploaded information is not automatically
stored into the RSNetWorx for DeviceNet software .dnt file.
You must make sure that you save any changes after you exit the
DeviceLogix Editor to ensure that any changes made to the
schematic are saved, including changes made as a result of an
upload.
2. Download Logic
To download logic, click the Download Logic icon, or
alternatively select Communications > Download. The logic
configuration in the Function Block Editor is duplicated and
transferred to the device. Before a download can be performed,
the logic must pass the verification process. See Verify Logic
for more information.
3. Logic Enable On
Use the Logic Enable On icon or alternatively select
Communications> Logic Enable On
in order to begin logic
execution. When set this parameter notifies the device to start
processing the stored logic diagram.
4. Logic Enable Off
Use the Logic Enable Off icon or alternatively
Communications > Logic Enable Off
in order to stop logic
execution. When set this parameter causes the device to enter an
idle state.
5. Compare Logic
Use the Compare option to determine if the logic in the Function
Block Editor matches the logic in the device. The results of the
comparison display in a pop up window. To use the compare
function select the Compare Logic icon, or select Tools >
Compare.