Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 299

B-124
Parameters
1503-UM054C-EN-P – June 2013
Loss of Input Line Power on IB5 [IB 5 Line Loss]
Parameter Number:
237,_,_,_,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-5-47
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of Loss of Input Line
Power fault from the IB5 module. If the bit is ‘0’ then the warning is
not present. If the bit is ‘1’ then the warning is present. See Supply
Voltage in Chapter 4 for a detailed description of this warning.
Main Coil Open on IB1 [IB 1 Main Coil Open]
Parameter Number:
238,197,156,115,73.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-1-48
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of Main Coil Open
fault from the IB1 module. If the bit is ‘0’ then the warning is not
present. If the bit is ‘1’ then the warning is present. See Open Coil
Test in Chapter 4 for a detailed description of this warning.
Main Coil Open on IB2 [IB 2 Main Coil Open]
Parameter Number:
239,198,157,116,_.
Access rule:
Get
Data Type:
USINT
Object Mapping:
0x384-2-48
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of Main Coil Open
fault from the IB2 module. If the bit is ‘0’ then the warning is not
present. If the bit is ‘1’ then the warning is present. See Open Coil
Test in Chapter 4 for a detailed description of this warning.