Pre configured logic mode, Figure 9.20 – select pre-configured logic program – Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 161

9-38
DeviceLogix
1503-UM054C-EN-P – June 2013
This is an example of a basic logical replacement for a typical relay
control circuit. Pushing the start pushbutton will cause the DLX1
Input 1 to go to “1” which is then tied to the “Net out 27/Start”
output tag which is a dual function bit which controls the “Start”
input tag. When this goes to “1” the output gate of the “OR” gate
goes to “1” and assuming the Normally closed “STOP” pushbutton is
not depressed the output of the “AND” gate will got to “1” and close
the contactor. The auxiliary input of the contactor will then close
which will keep the “OR” gate at “1”. This means the contactor will
remain closed until the “STOP” pushbutton is depressed.
Pre configured Logic Mode
:
The IntelliVAC Plus comes with five preprogrammed logic programs
corresponding to the 5 most common types of Rockwell Automation
MV controllers requiring multi contactor control. The five
preconfigured logic blocks are:
RVAT (reduced voltage autotransformer starter)
RVR (reduced voltage reactor starter)
FVR (full voltage reversing starter)
SMC (“smart motor controller” solid-state reduced voltage starter)
SMC+ PFCC (“smart motor controller” with the addition of
power factor correcting capacitors)
These control profiles can be selected in the device parameters page
in RSNetworx. They are located in the Control parameter group.
Figure 9.20 – Select Pre-Configured Logic Program