Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 259

B-84
Parameters
1503-UM054C-EN-P – June 2013
Jog Repetition Time for IB2
[IB 2 Jog Repetition Time]
Parameter Number:
154,130,106,82,_.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-2-22
Group:
Configuration
Units:
Seconds
Minimum Value:
0
Maximum Value:
60
Default Value:
6
This parameter allows the user to view and set the Jog Repetition
Time for contactor IB2. It indicates the amount of time between
successive Jog intervals. Therefore, once a Jog interval has begun, it
cannot be repeated until the Jog Repetition Time has elapsed for
contactor IB2. This is only for Electrically Held contactors and
makes use of the Open command. See Temporary Jog Function in
Chapter 4 for a more detailed description of this feature.
Jog Repetition Time for IB3
[IB 3 Jog Repetition Time]
Parameter Number:
155,131,107,_,_.
Access rule:
Get/Set
Data Type:
UINT
Object Mapping:
0x384-3-22
Group:
Configuration
Units:
Seconds
Minimum Value:
0
Maximum Value:
60
Default Value:
6
This parameter allows the user to view and set the Jog Repetition
Time for contactor IB3. It indicates the amount of time between
successive Jog intervals. Therefore, once a Jog interval has begun, it
cannot be repeated until the Jog Repetition Time has elapsed for
contactor IB3. This is only for Electrically Held contactors and
makes use of the Open command. See Temporary Jog Function in
Chapter 4 for a more detailed description of this feature.