Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 288

Parameters B-113
1503-UM054C-EN-P – June 2013
Module not Healthy on IB5 [IB 5 Module not Healthy]
Parameter Number:
212,_,_,_,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-5-28
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of the Module not
Healthy fault
from the IB5 module. If the bit is ‘0’ then the warning
is not present. If the bit is ‘1’ then the warning is present. See Table
4.E and related description for a detailed description of this warning.
Contactor not Healthy on IB1 [IB 1 Contactor Not Healthy]
Parameter Number:
213,177,141,105,68.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-1-56
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of the Contactor not
Healthy fault
from the IB1 module. If the bit is ‘0’ then the warning
is not present. If the bit is ‘1’ then the warning is present. See Table
4.E and related description for a detailed description of this warning.
Contactor not Healthy on IB2 [IB 2 Contactor Not Healthy]
Parameter Number:
214,178,142,106,_.
Access rule:
Get
Data Type:
BOOL
Object Mapping:
0x384-2-56
Group:
Diagnostics
Units:
-
Minimum Value:
0 = Not Present
Maximum Value:
1 = Present
Default Value:
0
This parameter allows the user to view the status of the Contactor not
Healthy fault
from the IB2 module. If the bit is ‘0’ then the warning
is not present. If the bit is ‘1’ then the warning is present. See Table
4.E and related description for a detailed description of this warning.