Rockwell Automation 1503VC IntelliVAC Plus Contactor Control Module User Manual
Page 254

Parameters B-79
1503-UM054C-EN-P – June 2013
Delay Restart Wait Time for IB2
[IB 2 Delay Restart Wait Time]
Parameter Number:
144,122,100,78,_.
Access rule:
Get
Data Type:
UINT
Object Mapping:
0x384-2-20
Group:
Configuration
Units:
Seconds
Minimum Value:
0
Maximum Value:
3600
Default Value:
0
This parameter allows the user to view the Delay Restart Wait Time
for IB2. It shows the time left, as a constantly updated real time,
after the contactor has closed, before it is permitted to close again.
This parameter works in conjunction with parameter #139 which
defines the minimum time allowed between successive closings of
contactor IB2. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.
Delay Restart Wait Time For IB3
[IB 3 Delay Restart Wait Time]
Parameter Number:
145,123,101,_,_.
Access rule:
Get
Data Type:
UINT
Object Mapping:
0x384-3-20
Group:
Configuration
Units:
Seconds
Minimum Value:
0
Maximum Value:
3600
Default Value:
0
This parameter allows the user to view the Delay Restart Wait Time
for IB3. It shows the time left, as a constantly updated real time,
after the contactor has closed, before it is permitted to close again.
This parameter works in conjunction with parameter #140 which
defines the minimum time allowed between successive closings of
contactor IB3. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.